Required Dedicated Circuits
- Two 20-amp small-appliance circuits for countertop outlets
- Refrigerator (20-amp)
- Dishwasher (20-amp)
- Garbage disposal (20-amp; can share with dishwasher under specific conditions)
- Microwave (20-amp built-in; countertop microwaves can be on small-appliance circuit)
- Electric range (240V, 40 or 50-amp)
- Gas range receptacle (20-amp)
Outlet Placement
Countertop outlets max 4 feet apart with none more than 2 feet from the end of a counter. Any countertop 12 inches or wider needs an outlet. Peninsula and island counters need at least one.
Need a licensed Orange County electrician?
Family-owned since 1974. C-10 #1050793 Licensed, Bonded & Insured. Serving all of Orange County.
Protection Required
All kitchen 15/20-amp outlets require GFCI protection. Combined AFCI/GFCI is required at countertop outlets.
Under-Cabinet and Island Considerations
Under-cabinet lighting typically runs on the general lighting circuit with a wall switch. Island outlets — surface, pop-up, or under-cabinet — all must be GFCI-protected.